30-minute IT shutdown
2 kW for 30 min at 48 V—~24.5 Ah planning floor before margin.
This UPS battery calculator sizes required battery Ah from load, target runtime, voltage, and efficiency. Use it for Ah planning—not a runtime-minutes estimator and not brand replacement shopping lists. Need backup minutes? Use the UPS Runtime Calculator. Need series/parallel blocks? Use the UPS Battery Bank Calculator. Start from the UPS calculator hub if you still need load or kVA.
This UPS battery calculator answers how many Ah you need for a target backup window—not how many minutes an existing pack will last. UPS battery Ah sizes the DC plant from load kW, target minutes, string voltage, efficiency, and DoD. Energy need ≈ load (kW) × hours, adjusted for inverter efficiency and DoD, then ÷ nominal V. Example: 2 kW for 30 minutes at 48 V with 0.85 efficiency → about 24.5 Ah before aging/temperature margin. For online (double-conversion) plants, plan η often 0.85–0.92. Get kW from the UPS load calculator, verify minutes in the UPS runtime calculator (minutes from known Ah—not Ah from minutes).
Opposite directions of the same energy math—use the matching tool URL.
| You know | You need | Open |
|---|---|---|
| Load kW + target minutes | Required Ah | UPS battery calculator (this page) |
| Load kW + existing V/Ah | Backup minutes | UPS runtime calculator |
Enter load and target runtime only. Required Ah, warnings, and recommended next steps below use the same load and minutes. Default 48 V string and 0.85 efficiency (adjust in Advanced).
Same load and target minutes as full results below. Quick defaults: 48 V, efficiency 0.85—change voltage or efficiency in Advanced.
Quick Examples
Estimates only. Verify with manufacturer battery tables, discharge-rate limits, and review by a qualified professional for binding designs.
Results
Energy (DC-equivalent): 1176 Wh (1.18 kWh)
Required battery: 24.5 Ah @ 48 V
Default: 2 kW, 30 min, efficiency 0.85.
Operational guidance
Typical IT ride-through
30 minutes at 2 kW is a common planning anchor—confirm discharge rate limits with the OEM.
| Runtime (min) | Ah @ 48 V |
|---|---|
| 10 | 8.2 |
| 20 | 16.3 |
| 30 (your target) | 24.5 |
| 45 | 36.8 |
| 60 | 49.0 |
Planning note: For VRLA UPS strings, many projects size on usable energy (DoD policy) rather than day-one nameplate. A common planning window is roughly 50–80% usable fraction and 0.85–0.92 DC-path/inverter efficiency (depends on topology and loading). If the battery room runs hot (often 25°C+), add Ah margin or reduce the target runtime before you lock string count.
Upstream: load, capacity. Cross-check minutes: UPS Runtime Calculator. Strings/blocks: UPS Battery Bank Calculator (series/parallel). Generic DC hours: battery runtime calculator. Scenario: how long will UPS last. Neighboring: cable size, voltage drop, breaker size.
Full four-step path: UPS calculator hub (load — capacity — runtime — battery).
2 kW for 30 min at 48 V—~24.5 Ah planning floor before margin.
5 kW for 15 min—higher discharge rate; verify OEM limits.
0.5 kW for 60 min at 48 V—light load, longer Ah at the same voltage.
~0.9 kW at 48 V with η 0.88 (double-conversion)—typical retail online frame; OEM charts override spreadsheet Ah.
30 min at 110 V cuts Ah versus 48 V for the same energy—confirm string count with the OEM.
Planning floor only—add aging/DoD margin and confirm OEM C-rate. Vendor-neutral alternative to APC/CyberPower/Eaton selectors that jump straight to product SKUs.
| Load | Target | ≈ Usable Ah @ 48 V |
|---|---|---|
| 2 kW | 15 min | ≈ 12.3 Ah |
| 2 kW | 30 min | ≈ 24.5 Ah |
| 5 kW | 15 min | ≈ 30.6 Ah |
| 0.5 kW | 60 min | ≈ 12.3 Ah |
| 2 kW | 30 min @ 110 V | ≈ 10.7 Ah |
After Ah is set, lay out series/parallel blocks in the UPS battery bank calculator, then verify minutes in the UPS runtime calculator.
Wh ≈ (kW × 1000 × runtime_min ÷ 60) ÷ η · usable Ah = Wh ÷ V · installed Ah = usable Ah ÷ DoD · Wh = Ah × V · kWh = Wh ÷ 1000.
C-rate screen: C ≈ (kW × 1000 ÷ (V × η)) ÷ installed Ah. See formula notes and worked examples below.
Amp-hours measure charge: for a constant current, Ah ≈ A × hours. UPS planning starts from energy (kW × time), then converts to Ah at string voltage. Depth of discharge (DoD)—sometimes called “depth of charge” in casual search—is the usable fraction of nameplate Ah. Installed Ah = usable Ah ÷ DoD. VRLA UPS strings often plan 0.50–0.80 DoD; setting DoD = 1.0 is an ideal nameplate case only.
Pure unit conversion (no UPS kW): Ah to Wh · Ah to amps.
Instant Wh to Ah / Ah to Wh at string voltage (same math as OEM energy labels).
100.00 Ah × 48 V = 4800.0 Wh (4.800 kWh)
Dedicated unit conversion: ampere hour to watt hour calculator. Generic DC pack hours: battery runtime calculator.
Field UPS plants rarely use a single cell string. Series strings raise nominal DC voltage (more V → fewer Ah for the same energy); parallel strings add amp-hour capacity and share discharge current. The calculator above gives a planning Ah at your entered voltage—multiply by parallel string count only when each string meets OEM C-rate and end-of-discharge limits.
Example: 2 kW for 30 minutes at 48 V needs ~25 Ah before margin. Two parallel 48 V strings of 50 Ah each may meet energy, but each string must still tolerate the discharge rate at your load step. Confirm string count, fuse/breaker layout, and rack weight with the battery OEM before ordering.
Deep dive: How to calculate UPS battery size (strings, margin, and vendor tables). Lay out blocks in the UPS battery bank calculator (how many batteries / series — parallel). Cross-check minutes in the UPS runtime calculator.
Vendors embed chemistry-specific curves, temperature coefficients, and minimum cell voltages. Use this calculator for directional planning, then finalize strings with OEM tools and stamped project documentation where required.
Yes. End-of-life capacity is lower than day-one ratings; prudent designs reserve Ah so degraded strings still meet the runtime contract at the design horizon.
Higher efficiency reduces DC energy required for the same AC load, which lowers Ah at a fixed voltage. Efficiency varies with load level, so use vendor curves near your true operating point.
No. You also need maximum discharge current, terminal layout, breaker coordination, recharge current limits, and physical rack constraints—Ah is necessary but not sufficient.
Series connections increase nominal voltage; parallel connections add amp-hours and share current. Total installed Ah must satisfy both energy math and per-string C-rate limits—see the strings and banks section above.
Use this page for quick Ah from kW and minutes. For string layout, aging margin, and OEM discharge tables, follow How to calculate UPS battery size.
Runtime estimates minutes from known battery parameters; this step estimates Ah when minutes and load drive procurement. Move between the tools as your knowns change.
Wh = Ah × V; Ah = Wh ÷ V; kWh = Wh ÷ 1000. Use the Wh ↔ Ah converter on this page, or the results card after you size Ah.
C-rate ≈ discharge amps ÷ installed Ah. Example: ~49 A on a 100 Ah string ≈ 0.5C. The results card shows a C-rate screen for your inputs—exceeding OEM max C-rate means add parallel strings or larger Ah.
Many VRLA UPS designs plan 0.50–0.80 usable DoD, not 1.0 of nameplate. Set DoD in Advanced: installed Ah = usable Ah ÷ DoD. Shallow DoD extends calendar and cycle life. Searches for “batteries DoD” or “depth of charge battery” usually mean this same usable-fraction policy.
Charge: Ah ≈ A × hours. UPS sizing from load: convert kW × minutes to Wh, then Ah = Wh ÷ V, then apply DoD. Energy labels: Wh = Ah × V—or use the Ah to Wh calculator.
Yes. This page is the UPS battery calculator for required Ah from load kW and target minutes. For backup minutes from known Ah/V/strings, use the UPS runtime calculator instead.
No—this page sizes UPS Ah from load kW and target minutes. For generic DC battery runtime / life (Ah × V ÷ W → hours), use the battery runtime calculator. For UPS inverter minutes, use UPS runtime.
Ah = (kW × 1000 × minutes ÷ 60) ÷ (V × efficiency). Online double-conversion UPS typically plans at 0.85–0.92 inverter efficiency at partial load—lower η increases required Ah versus standby at the same kW. Example: 0.9 kW for 30 min at 48 V with η 0.88 needs about 10.7 Ah before aging margin. Cross-check minutes in the runtime calculator and topology notes in the online vs offline UPS guide.
Not exactly. This page answers how many Ah do I need when load and target backup time are known. Tools titled —battery backup calculator— often estimate how long existing batteries will last—use the UPS runtime calculator for that direction, then return here for procurement Ah.
High ambient temperature accelerates VRLA aging and lowers usable capacity under load. A common planning rule: every 10°C above ~20°C can roughly halve calendar life—add 10–20% Ah margin or reduce assumed runtime when the battery room runs hot. Confirm on OEM temperature derating curves.
Combine semi-annual internal ohmic/impedance trending against baseline, periodic load tests at design kW, and float-voltage logs. When impedance rises past OEM limits (often +30–35% vs baseline) or a load test misses target minutes, plan string replacement—even if float voltage looks normal.
Battery amp-hour (Ah) sizing answers whether the DC plant can deliver enough energy for the target minutes at the protected AC load. Conceptually, you convert load power (kW) and required backup time into an energy demand (kWh), translate that to DC watt-hours using practical inverter and cable efficiency assumptions, then divide by the string voltage to obtain an amp-hour requirement before manufacturer derating curves.
Higher DC bus voltage reduces amp-hour for the same energy because each amp-hour carries more watt-hours when multiplied by a larger voltage. Temperature, end-of-discharge voltage, aging, and desired depth of discharge all increase the installed Ah relative to a naive arithmetic estimate—your battery vendor tables remain authoritative for final cell selection.
This calculator is positioned after load and runtime intent are understood. Treat its output as a planning anchor, then validate against UPS manufacturer software, battery tables, and local codes governing ventilated battery rooms and maintenance access.
Planning anchor: DC energy (Wh) ≈ (Load kW × Runtime hours) ÷ Overall DC-path efficiency; Ah ≈ DC energy (Wh) ÷ Nominal battery voltage (V)
Overall efficiency bundles inverter conversion, cable loss, and conservative headroom; exact factors vary by topology and state of charge.
Always round up to the next commercial block or string count and apply aging margin recommended by the battery OEM.
Half an hour at 2 kW implies about 1 kWh of AC-side energy before efficiencies. At 48 V, the naive amp-hour floor is roughly 21 Ah before inverter loss, temperature derating, and end-of-life margin—field designs normally select a materially larger bank.
For the same energy demand, moving from 48 V to 110 V cuts the amp-hour requirement roughly in proportion to the voltage ratio because watt-hours per string increase with voltage for the same current profile.
Five minutes at the same kW needs one-sixth of the energy of thirty minutes, but very short windows still require attention to discharge rate limits—some chemistries prefer longer, gentler discharges than aggressive high-rate bursts.