240 V IT UPS · 200 Ah
20 × 12 V series per string; two parallel 100 Ah strings → 40 blocks, 200 Ah installed at 240 V.
Answer “how many batteries do I need” with series blocks × parallel strings for 48 V, 110 V, 240 V, and custom UPS DC buses. This is a UPS string layout tool—not a solar / off-grid battery bank size (kWh × days) calculator.
How many batteries? Total blocks = series × parallel. Series raises voltage to the UPS bus (e.g. 20 × 12 V for 240 V). Parallel adds Ah (e.g. 200 Ah needed with 100 Ah blocks → 2 strings). Example: 20S × 2P = 40 blocks (400 Ah installed). Workflow: UPS Battery Calculator (Ah) → this bank layout → runtime check. Searching for a generic battery bank calculator / off-grid kWh bank? Use the solar battery bank calculator. Hub: UPS calculator.
Defaults: 200 Ah @ 240 V, 12 V × 100 Ah blocks, 10% aging margin.
20 × 12 V in series per string · 3 parallel strings · 300 Ah installed.
Quick Examples
Planning only. C-rate, fuse per string, rack weight, and OEM discharge tables override block counts—verify with vendor tools.
Results
60 blocks (20S × 3P) — default example.
Operational guidance
Bank meets planning Ah
Installed 300 Ah covers the planning target—confirm C-rate, rack weight, and fuse layout with the OEM before ordering.
| Block Ah | Total blocks |
|---|---|
| 26 | 180 |
| 38 | 120 |
| 55 | 80 |
| 65 | 80 |
| 100 (your value) | 60 |
| 120 | 40 |
| 200 | 40 |
Answers “series parallel battery calculator” style questions for UPS banks—what changes when you series or parallel 12 V blocks.
| Connection | Voltage | Ah | Use when |
|---|---|---|---|
| Series only | Adds (12×N) | Same as one block | Match UPS DC bus |
| Parallel only | Same as one block | Adds (Ah×M) | Need more Ah / lower C-rate |
| Series-parallel | 12×N | Ah×M | Real UPS banks (N×M blocks) |
| Layout | Bus V | Installed Ah | Total blocks |
|---|---|---|---|
| 4S1P · 100 Ah blocks | 48 V | 100 Ah | 4 |
| 4S2P · 100 Ah blocks | 48 V | 200 Ah | 8 |
| 20S1P · 100 Ah blocks | 240 V | 100 Ah | 20 |
| 20S2P · 100 Ah blocks | 240 V | 200 Ah | 40 |
Common buses: 48 V → 4×12 V; 110–120 V class → ~10×12 V; 240 V → 20×12 V. Enter your required Ah above to size parallel strings.
20 × 12 V series per string; two parallel 100 Ah strings → 40 blocks, 200 Ah installed at 240 V.
4 × 12 V series; one 100 Ah string → 4 blocks (or 2P if you need 200 Ah).
If you need days of autonomy from daily kWh, use the solar battery bank calculator—not series/parallel UPS blocks.
Series blocks = ⌈String V ÷ Cell V⌉ · Parallel strings = ⌈Planning Ah ÷ Block Ah⌉ · Total blocks = Series × Parallel
Ah energy first: UPS Battery Calculator. Wh/kWh units: Ah to Wh / kWh.
Yes for UPS string layout (how many 12 V blocks in series/parallel). For solar / off-grid battery bank size in kWh and autonomy days, use the solar battery bank calculator.
Total blocks = series count × parallel strings. Series count matches the UPS DC bus (for example 20 × 12 V for 240 V). Parallel strings = ceil(required Ah ÷ block Ah). Get required Ah from the UPS battery calculator first, then order blocks here.
Twenty blocks in series per string. Parallel strings depend on required Ah and each block Ah rating.
Series sets bus voltage; parallel sets Ah. Example: 20S2P of 100 Ah / 12 V blocks → 240 V and 200 Ah installed (40 blocks). Use the tables above, then enter required Ah in this calculator.
Three batteries only work if series/parallel match bus voltage and Ah. Three 12 V blocks in series make 36 V—not a typical 48 V or 240 V industrial bus. Size series for string voltage, then add parallel strings for capacity.
A string is a series chain of blocks that reaches the UPS nominal DC bus voltage. Parallel strings share discharge current and add amp-hours.
Battery calculator gives total Ah. This tool splits Ah into series blocks and parallel strings for ordering.
Yes—switch to energy mode or use the battery calculator first, then enter required Ah here.
Set cell voltage to 2 V; series count = string voltage ÷ 2. Confirm with OEM string diagrams.
Verify minutes in the runtime calculator with parallel strings and block Ah filled in. For generic DC pack hours, use battery runtime.
Battery bank layout converts planning amp-hours at a UPS DC bus voltage into orderable blocks—series count for string voltage and parallel strings for total Ah using commercial block ratings.
Series blocks multiply cell voltage to match the UPS nominal bus. Parallel strings add amp-hour capacity and share discharge current subject to OEM C-rate limits.
Use the UPS battery calculator for Ah energy sizing first, then this tool for procurement layout, then the runtime calculator to verify minutes with strings entered.
Series = ceil(String V / Cell V); Parallel = ceil(Planning Ah / Block Ah); Total blocks = Series × Parallel
Planning Ah includes aging margin applied before parallel string count.
Actual string voltage may differ slightly from nominal bus when block count is rounded up.
Twenty 12 V blocks in series per string; two parallel strings of 100 Ah blocks yields 40 blocks and 400 Ah installed.